Calculators

Cable cross-sectional area and MCB

What cable do I run and what MCB do I fit for this load?

Advanced conditions and parameters · Copper · B2 · 30 °C

Result

Minimum cross-sectional area1.5mm²
Recommended MCBC10A
Design current9.15A
Corrected current-carrying capacity13.5A
Correction factor applied1.000
Voltage drop1.35%

The cross-sectional area follows from the current-carrying capacity, so it is the thermal minimum. Annex 5.32 sets minimums per type of circuit that can be larger (2.5 mm² for socket outlets), and the voltage drop over the route length is checked separately. Minimum cross-sectional area by type of circuit

Calculation assumptions

The result holds under the conditions below. If your situation differs, change the values in the advanced section.

  • power factor cos φ = 0.95
  • ambient temperature 30 °C
  • run in conduit concealed in a wall (method B2)
  • a single circuit in the conduit, no grouping
  • PVC insulation, 70 °C at the conductor
  • copper conductor
  • overload coefficient 1.25 per IEC 60364-5-52
  • 230 V single-phase / 400 V between lines on three-phase

Want the explanation? →

The results are indicative and do not replace a design checked by a registered electrician. Every tool states its assumptions.