Phase balancing in a dwelling
Which phase do I connect each appliance to, so that L1, L2 and L3 come out as balanced as possible?
Checks the whole connected load switched on at once — what the editor’s imbalance rule sees too. Quick, but pessimistic: every appliance on at the same time is not a real situation.
You start from scratch: the calculation picks each appliance’s phase. You can pin an appliance’s phase in its advanced parameters.
Appliances in the home · 14 appliances
Result
Proposed split
By phase, with the whole connected load on at once — the appliances and their position:
8.40 kW
- Induction hob → L1+L2
- Air conditioner → L1
- Outdoor lighting → L1occasional
- Kitchen socket-outlets → L1
- Kettle → L1
8.25 kW
- Induction hob → L1+L2
- Oven → L2
- Refrigerator → L2
- Bedroom lighting → L2occasional
- Bedroom socket-outlets → L2occasional
8.40 kW
- Washing machine → L3
- Dishwasher → L3
- Storage water heater → L3
- Living area lighting → L3occasional
- Living room socket-outlets → L3occasional
Lights and socket-outlets with no fixed appliance, circuits on each phase:
- Lighting: L1 1 · L2 1 · L3 1
- Socket-outlets: L1 0 · L2 1 · L3 1
(max − min)/average. The 15 % / 30 % thresholds are the app’s convention (rule V43) — Art. 3.1.5.8 requires the phases to be loaded as evenly as possible, but gives no figure.
At the fundamental, without harmonics. With different power factors it can exceed the phase current.
Sum with phase angles, for information only; the split is made on the arithmetic current above.
Proven optimal: among the splits that put lights and socket-outlets with no fixed appliance across all three phases, none gives a lower maximum phase current.
Greedy: 39.6 A · Optimal: 37.3 A (maximum phase, whole connected load)
Calculation assumptions
The result holds under the conditions below. If your situation differs, change the values in the advanced section.
- the powers are the input powers from the appliance labels; while it is on, an appliance counts at full power
- the split is optimised on the arithmetic current per phase, Σ P/(U·λ) — greater than or equal to the real current, because it ignores the phase angle between appliances (on the safe side)
- the phasor currents and the neutral current are calculated at the fundamental (50 Hz), with cos φ = λ, without harmonics
- 230 V single-phase / 400 V between lines on three-phase
- the 15 % and 30 % imbalance thresholds are the app’s convention (rule V43); I7-2011 Art. 3.1.5.8 requires the phases to be loaded as evenly as possible, without giving a figure
- lights and socket-outlets with no fixed appliance are split across all three phases (at most one more on any phase than on another); in Advanced and Advanced+, at most as many as set under “In use at the same time” count as on at once on each phase, the largest ones, and in Simple all of them, at full power
The results are indicative and do not replace a design checked by a registered electrician. Every tool states its assumptions.