Exercises · Calculators

Interactive compliance calculators

Calculation tools per I7-2011 and IEC 60364: cable cross-sectional area sizing by current and installation method, voltage drop check per circuit. The formulas are shown step by step.

Cable sizing calculator

Minimum cross-sectional area per I7-2011 Table 5.1 + IEC 60364-5-52

0.85 typical residential, 1.0 purely resistive

K1 — Annex 5.18 (reference 30°C, PVC insulation)

K2 — Annex 5.19 (1 = a single circuit)

Affects K1 (XLPE withstands heat better)

Factor 0.86 — Annex 5.29 (LED, switched-mode supplies)

Conservative derating ~0.93 (dry/sandy soil)

Current-carrying capacity table (Cu + Al, concealed B2) — I7-2011 reference
Cross-sectional area (mm²)1.52.54610162535
I max Cu (A) · B215212836506684104
I max Al (A) · B2222839526682

Voltage drop calculator

Check against the 3% limit (lighting) / 5% (sockets) — I7-2011 Art. 5.2.5.1

Art. 5.2.5.1 I7-2011: The total voltage drop must not exceed 3% for lighting circuits and 5% for other circuits, calculated from the origin of the installation to the most remote point of use.
Conductivity: Cu = 56 m/(Ω·mm²), Al = 35 m/(Ω·mm²) at 70°C per IEC 60228.

Calculation assumptions and scope

  • Included: Cu/Al material, single-phase/three-phase, B2/F installation, PVC/XLPE insulation, K1 (temperature, Annex 5.18), K2 (grouping, Annex 5.19), 3rd-order harmonics (0.86, Annex 5.29), dry-soil derating and the 10 mm² minimum cross-sectional area for Al (Art. 5.2.4.6.1(d))
  • The "dry soil" factor is a conservative estimate (~0.93) applied to table B2; for accurate sizing of buried cables use the in-ground installation table (method D, Annexes 5.22–5.28)
  • Tabulated current-carrying capacities for PVC insulation at 70°C (XLPE is adjusted via K1); voltage drop calculated using the resistivity at 70°C
  • For complex industrial installations, validate the result with a full calculation + short-circuit check (breaking capacity + thermal stability)
Guide

How it’s calculated — step by step

The full method per I7-2011 / IEC 60364, from power to cross-sectional area, length and voltage drop.

A. The operating current — the starting point

1

Work out the current drawn from the power

Single-phase: I = P / (U × cos φ), U = 230 V
Three-phase: I = P / (√3 × U × cos φ), U = 400 V

E.g.: a 2000 W socket, cos φ = 0.9 → I = 2000 / (230 × 0.9) = 9.66 A.

B. Choosing the cable cross-sectional area (with K correction factors)

1

Start from the operating current I (step A)

E.g.: I = 16 A.

2

Apply the 25% safety margin (IEC 60364-5-52 Art. 523)

I_design = I × 1.25

16 × 1.25 = 20 A.

3

Apply the K correction factors (real-world conditions)

K = K1 (temperature, Annex 5.18) × K2 (grouping, Annex 5.19) × K_harmonics × K_soil

At 30 °C and a single circuit, K = 1. At 40 °C + 3 grouped circuits: K = 0.87 × 0.70 = 0.609.

Additional factors (all in the calculator above): 3rd-order harmonics → 0.86 (Annex 5.29); dry soil / in-ground installation → derating; XLPE insulation adjusts K1.

4

Choose the cross-sectional area: the first in the table with Iz × K ≥ I_design

Iz_table × K ≥ I_design (equivalent: Iz_required = I_design / K)

Ideal case (K=1): 20 A → 2.5 mm² (21 A). Real case (K=0.609): 20 / 0.609 = 32.8 A → 6 mm² (36 A).

Cross-sectional area (mm²)1.52.5461016
Iz B2 Cu (A)152128365066
Al cross-sectional area (mm²)10162535
Iz B2 Al (A)39526682

Iz tables for B2 installation, PVC insulation (Cu and Al conductors): I7 Annex 5.10 / NTE 007/08/00 (XLPE: Annex 5.13). Aluminium — minimum cross-sectional area 10 mm² (Art. 5.2.4.6.1(d)).

C. The real cable length

1

Measure the horizontal route on the plan

The sum of the horizontal segments between consumer unit → junction boxes → equipment.

2

Add the vertical drops/rises (mounting heights)

junction box 2.0 m · socket 0.3 m · switch 1.3 m · light/ceiling 2.6 m

E.g.: from the junction box (2.0 m) to the socket (0.3 m) → drop = 2.0 − 0.3 = 1.7 m.

3

Add the floor-to-floor crossings (slab height)

~2.6–3 m per floor crossed.

4

Add it all up

E.g.: 8 m horizontal + 1.7 m socket drop = 9.7 m.

D. Voltage drop over the length

1

Apply the voltage drop formula

ΔU% = (factor × L × P) / (k × S × U²) × 100

factor = 2 (single-phase, out and back) or 1 (three-phase); k = 56 (Cu) / 35 (Al); S = cross-sectional area (mm²).

2

Quick rule (single-phase, copper)

ΔU% ≈ (L × P) / (14800 × S)

E.g.: L = 20 m, P = 2000 W, S = 2.5 → 20 × 2000 / (14800 × 2.5) ≈ 1.08 %.

3

Compare with the regulatory limit (I7-2011 Art. 5.2.5.1)

3 % for lighting, 5 % for sockets/power. If you exceed it → increase the cross-sectional area or shorten the route.

Conductivity k per IEC 60228 (Cu 56, Al 35 m/Ω·mm²). Voltage drop limits: I7-2011 Art. 5.2.5.1.

E. Copper (Cu) vs. Aluminium (Al)

AspectCopper (Cu)Aluminium (Al)
Conductivity k5635 → ~60% more voltage drop
Current-carrying capacityreference~78% of Cu → larger cross-sectional area
Minimum cross-sectional area1.5 mm²10 mm² (Art. 5.2.4.6.1(d))
Typical useindoor circuitsservice connection / distribution circuit

In the formulas, the only change is k (56 → 35) and the current-carrying capacity table. The Cu/Al toggle in the comparator below applies both automatically.

K1 — temperature (PVC, Annex 5.18)

°C3035404550
K110.940.870.790.71

K2 — circuit grouping (Annex 5.19)

circ.1234
K210.80.70.65
Comparison

Single-phase vs. three-phase

The same calculations, but 3 differences that matter. Enter a power and see both options at once.

QuantitySingle-phase (230 V)Three-phase (400 V)
CurrentI = P/(230·cosφ)I = P/(√3·400·cosφ)
Voltage dropfactor 2 · U = 230factor 1 · U = 400
ConductorsL + N + PER + S + T + N + PE
Protection1P+N3P / 4P · R/S/T balancing

At the same power, three-phase "draws" ~1/3 of the current (→ smaller cross-sectional area) and has ~6× less voltage drop.

Conductor material:

Single-phase · 230 V

Current I = P/(230·cosφ)31.3 A
Cross-sectional area (×1.25)10 mm²
Drop ΔU% (factor 2)0.97 %

Three-phase · 400 V

Current I = P/(√3·400·cosφ)10.4 A
Cross-sectional area (×1.25)1.5 mm²
Drop ΔU% (factor 1)1.07 %

Three-phase / single-phase current = 230 / (√3 × 400) = 0.33 (≈ 1/3)

Cross-sectional area: 1.5 mm² (three-phase) vs 10 mm² (single-phase), same power

At the same cross-sectional area, the three-phase drop would be 6.0× smaller (factor 1 vs 2 and 400² vs 230²)

Level 1 · Guided

Exercises — pick the correct option

You go through each step by choosing the correct answer. Wrong? Try again.

Cross-sectional area — kitchen socket

A socket circuit feeds a 3000 W appliance (single-phase, cos φ = 1), B2 installation, at 30 °C, a single circuit.

Step 1: What is the operating current I = P / (U × cos φ)?

Length — route to the socket

The consumer unit → socket route is 6 m horizontal on the plan. The junction box is at 2.0 m, the socket at 0.3 m.

Step 1: What is the vertical drop from the junction box to the socket?

Voltage drop — socket circuit

Socket circuit, L = 25 m, P = 2200 W, 2.5 mm² Cu cross-sectional area, single-phase.

Step 1: What factor do you use in the formula (single-phase)?

Cross-sectional area with K factors — water heater in a hot loft

2000 W water heater (single-phase, cos φ = 1), mounted in a loft at 45 °C, grouped with 2 other circuits (3 in total).

Step 1: The operating current?

Level 2 · Guided calculation

Exercises — you calculate each step

Now you enter the value for each step yourself. You get hints if you go wrong.

Cross-sectional area — air conditioning (you calculate)

1800 W AC unit (single-phase, cos φ = 0.9), at 35 °C, grouped with one more circuit (2 in total). Use the tables above.

Step 1: The operating current I = P / (U × cos φ) = ?

A

Length — two components

Consumer unit → junction box route = 9 m horizontal. The junction box at 2.0 m, the socket right below it at 0.3 m.

Step 1: Vertical drop junction box → socket = ?

m

Voltage drop — the full formula

L = 30 m, P = 3000 W, 4 mm² Cu cross-sectional area, single-phase. Formula: ΔU% = (2 × L × P) / (56 × S × 230²) × 100.

Step 1: ΔU% = ?

%

Cross-sectional area — three-phase hob

7200 W three-phase hob (cos φ = 1), 30 °C, one circuit. Three-phase: I = P / (√3 × 400 × cos φ).

Step 1: The operating current = ?

A

Voltage drop — ALUMINIUM distribution circuit

Aluminium distribution circuit: L = 30 m, P = 6000 W, 16 mm² cross-sectional area, single-phase. For aluminium k = 35 (not 56 as for copper).

Step 1: ΔU% on aluminium = ?

%
Level 3 · Independent

Exercises — direct answer

You solve it on your own and give the final answer. The step-by-step solution is available if needed.

Cross-sectional area — oven

2500 W oven (single-phase, cos φ = 1), 30 °C, one circuit. Which minimum cross-sectional area do you choose (mm²)?

mm²

Total length

15 m horizontal route + drop from the junction box (2.0 m) to the socket (0.3 m). What is the cable length (m)?

m

Voltage drop

L = 40 m, P = 2000 W, 2.5 mm² Cu cross-sectional area, single-phase. What is ΔU% (percentage)?

%

Cross-sectional area with K factors

4000 W load (single-phase, cos φ = 1), at 40 °C, grouped with 2 other circuits (3 total). Which cross-sectional area (mm²)?

mm²

Cross-sectional area — ALUMINIUM cable

3000 W load (single-phase, cos φ = 1), but an aluminium cable. Which minimum cross-sectional area (mm²)? Watch the Al minimum.

mm²

Discussion

Comments are moderated before publication. Your email is not displayed publicly.